Powerware 9170 User Manual page 53

3–18 kva, 50 and 60 hz
Hide thumbs Also See for 9170:
Table of Contents

Advertisement

9.
EPO circuits are not isolated from line voltage, and wiring must be installed
according to local codes using conduit or suitable primary supply cables.
10.
NOTE
Generator On wires.
+
Powerware
9170
UPS User's Guide
®
If any external hardwired control signals are required (EPO or
Generator On), unscrew and remove the top rear panel of the
cabinet and locate the terminal block (see Figure 31).
C A U T I O N
The Generator On signal is isolated from line voltage and can be
treated as NEC Class 2 wiring.
Use 14–20 AWG, 600V wire (UL) or 14–26 AWG, 300V wire
(CSA) for all input control signals.
Generator On
(Normally Open)
Emergency Power-Off (Normally Closed)
External Bypass *(Short to Common When Active)
Generator Set
Figure 31. Input Control Signal Wiring
Place the signal wires through the proper conduit or grommet
above the terminal block and attach to appropriate terminals.
Secure each connection by torquing terminal screws to a
maximum 3.5 in lb (0.4 Nm). Provide strain relief for cables by
installing plastic cable ties.
Do not strain relieve EPO wiring with the same cable tie used for
Rev B www.powerware.com
S
UPS Electrical Installation
Signal
Common
Plastic Cable Tie
45