Powerware 9170 User Manual page 31

3–18 kva, 50 and 60 hz
Hide thumbs Also See for 9170:
Table of Contents

Advertisement

NOTE
the input terminals inside the UPS.
Table 3. Bypass Switch Positions
Switch Position
LINE
Connects the load directly to AC input power and disconnects UPS output. AC input
power is still connected to the UPS input.
OFF
Disconnects the load from the UPS output power and AC input power, as well as AC
input power to the UPS input.
UPS
Connects the UPS output to the load.
SERVICE
Like the LINE position, SERVICE connects the load directly to AC input power and
disconnects UPS output.
from the UPS, this is the appropriate position for UPS maintenance or
repair.
To disconnect AC input power during maintenance or service, turn the
bypass switch to the SERVICE position. For MBB switches, you must press
the red button beside the switch before you can change the switch
position.
Table 4 shows the bypass switch models available for the Powerware
9170
Table 4. Bypass Switch Specifications
Bypass Switch Models
BBM
MBB
BPE12BBM1A
BPE12MBB1A
BPE14BBM1A
BPE14MBB1A
BPE20BBM1A
BPE20MBB1A
+
Powerware
9170
UPS User's Guide
®
In the UPS or LINE position, AC input power is still connected to
However, because SERVICE also disconnects AC input
+
UPS.
Rating,
R ti
Height
Continuous
Continuous
(A)
40A/300 Vac
21.0I
(CSA)
(53.4 cm)
(35.6 cm)
50A/300 Vac
(UL,TÜV)
80A/300 Vac
21.0I
(53.4 cm)
(35.6 cm)
125A/300 Vac
21.0I
(53.4 cm)
(35.6 cm)
Rev B www.powerware.com
S
UPS with Bypass Electrical Installation
Description
See Figure 14
Width
Depth
Mounting Centers
(B)
(C)
(D)
14.0I
6.8I
11.0I
(17.2 cm)
(28.0 cm)
14.0I
6.8I
11.0I
(17.2 cm)
(28.0 cm)
14.0I
6.8I
11.0I
(17.2 cm)
(28.0 cm)
Weight
(E)
20.0I
27 lb
(50.8 cm)
(12.3 kg)
20.0I
31 lb
(50.8 cm)
(14.1 kg)
20.0I
35 lb
(50.8 cm)
(15.9 kg)
23