Powerware 9170 User Manual page 109

3–18 kva, 50 and 60 hz
Hide thumbs Also See for 9170:
Table of Contents

Advertisement

Table 18. Environmental and Safety
Operating Temperature
0°C to 40°C (32°F to 104°F)
Optimal battery performance: 25°C (77°F)
Storage Temperature
UPS with battery modules: –20°C to +40°C (–4°F to 104°F)
UPS without batteries: –40°C to +60°C (–40°F to 140°F)
Relative Humidity
5–95% noncondensing
Operating Altitude
Up to 3,050 meters above sea level (10,000 ft)
The maximum operating ambient temperature decreases 1°C per 300m above
1525m (2°F per 1000 ft above 5000 ft)
Non-Operating Altitude
Up to 12,200 meters above sea level (40,000 ft)
Ventilation
The air around the UPS must be clean and free of dust, corrosive chemicals, and
other contaminants. The Powerware 9170
air for cooling. The air must be free to circulate around the UPS and battery
cabinet(s). Do not operate the UPS in a sealed room or container.
Audible Noise
Less than 53 dBA
Surge Suppression
ANSI C62.41 Category B (formerly IEEE 587); IEC 61000-4-5
Safety Conformance
CAN/CSA C22.2, No. 107.1; UL 1778;
EN 50091-1-1 and IEC 60950
Agency Markings
UL, cUL, TÜV, CE, C-Tick, BCIQ
EMC (Class A)
EN 50091-2, FCC Part 15, ICES-003, VCCI
Table 19. Battery
Configuration
(2) 60V, 7.2 Ah batteries per string
Voltage
120 Vdc
Type
Sealed, maintenance-free, valve-regulated, lead-acid
Charging
Recharge time: 4 hr after full-load resistive discharge; 8 hr after half-load
resistive discharge, using standard internal battery charger.
Optional battery chargers at higher current ratings will be available for future
product release.
+
Powerware
9170
UPS User's Guide
®
Rev B www.powerware.com
S
Specifications
+
UPS uses internal fans to circulate the
101