3–18 kva, 50 and 60 hz
Hide thumbs Also See for 9170:
Table of Contents

Advertisement

Specifications
Table 16. Split-Phase Model Specifications (ASY-0673) Continued
Voltage
Input Current*
200
64A
220
60A
208
56A
220
52A
230
58A
240
56A
Voltage
Input Current*
200
80A
220
75A
208
70A
220
65A
230
72.5A
240
70A
Voltage
Input Current*
200
96A
220
90A
208
84A
220
78A
230
87A
240
84A
*In High-Efficiency and Bypass modes the input current equals the output current plus 2A for each power
module in the system.
For redundant power module operation (N+X), increase the input current rating by 2A for each additional
redundant power module.
98
12 kVA, 10000 Watts
Output Current
Input Service*
60A
56A
58A
80A
80A
56A
52A
50A
15 kVA, 12500 Watts
Output Current
Input Service*
75A
70A
72.5A
100A
100A
70A
65A
62.5A
18 kVA, 15000 Watts
Output Current
Input Service*
90A
84A
77A
125A
125A
84A
78A
75A
+
Powerware
9170
UPS User's Guide
®
Heat Dissipation
Normal Mode
1145W (3.90 kBTU/hr)
1145W (3 90 kBTU/hr)
Heat Dissipation
Normal Mode
1430W (4.88 kBTU/hr)
1430W (4 88 kBTU/hr)
Heat Dissipation
Normal Mode
1720W (5.85 kBTU/hr)
1720W (5 85 kBTU/hr)