Table 17. Universal Model Specifications (ASY-0674)
Voltage
Input Current*
200
14A
208
13.5A
220
13A
230
12.5A
240
12A
Voltage
Input Current*
200
28A
208
27A
220
26A
230
25A
240
24A
Voltage
Input Current*
200
42A
208
40.5A
220
39A
230
37.5A
240
36A
*In High-Efficiency and Bypass modes the input current equals the output current plus 2A for each power
module in the system.
For redundant power module operation (N+X), increase the input current rating by 2A for each additional
redundant power module.
+
Powerware
9170
UPS User's Guide
®
3 kVA, 2100 Watts
Output Current
15A
14.5A
14A
13A
12.5A
6 kVA, 4200 Watts
Output Current
30A
29A
28A
26A
25A
9 kVA, 6300 Watts
Output Current
45A
43.5A
42A
39A
37.5A
Rev B www.powerware.com
S
Heat Dissipation
Input Service*
Normal Mode
25A
285W (0.98 kBTU/hr)
(
Heat Dissipation
Input Service*
Normal Mode
40A
570W (1.95 kBTU/hr)
(
Heat Dissipation
Input Service*
Normal Mode
60A
860W (2.93 kBTU/hr)
(