UPS Electrical Installation
5.
6.
42
Figure 27 shows input and output wiring terminals inside the
+
Powerware 9170
UPS cabinet.
+DC
X2
Backplane
Board
Terminating
Studs
X2
+DC
Figure 27. UPS Input and Output Terminals
Wire the UPS for the proper input voltage as shown in
Figure 28.
Split-phase power modules (model ASY-0673, with brown labels
on the front) is capable of supplying two output voltages:
100/100 for 200, 110/110 for 220, 120/120 for 240, 120/120
for 208, or 127/127 for 220 Vac, as selected through the front
panel display. These modules produce two output voltages,
typically required in North America, South America, and Japan.
Universal power modules (model ASY-0674, with black labels on
the front) is capable of supplying a single-phase output voltage:
200, 208, 220, 230, or 240 Vac, as selected through the front
panel display. These modules produce a single output voltage,
typically required in Europe, the Middle East, Asia, and Africa.
+
Powerware
9170
UPS User's Guide
®
3
2
1
N
-DC
X1
N
X1
-DC
Rev B www.powerware.com