Powerware 9170 User Manual page 105

3–18 kva, 50 and 60 hz
Hide thumbs Also See for 9170:
Table of Contents

Advertisement

Table 16. Split-Phase Model Specifications (ASY-0673)
Voltage
Input Current*
200
16A
220
15A
208
14A
220
13A
230
14.5A
240
14A
Voltage
Input Current*
200
32A
220
30A
208
28A
220
26A
230
29A
240
28A
Voltage
Input Current*
200
48A
220
45A
208
42A
220
39A
230
43.5A
240
42A
*In High-Efficiency and Bypass modes the input current equals the output current plus 2A for each power
module in the system.
For redundant power module operation (N+X), increase the input current rating by 2A for each additional
redundant power module.
+
Powerware
9170
UPS User's Guide
®
3 kVA, 2500 Watts
Output Current
15A
14A
14.5A
14A
13A
12.5A
6 kVA, 5000 Watts
Output Current
30A
28A
29A
28A
26A
25A
9 kVA, 7500 Watts
Output Current
45A
42A
43.5A
42A
39A
37.5A
Rev B www.powerware.com
S
Heat Dissipation
Input Service*
Normal Mode
25A
25A
285W (0.98 kBTU/hr)
285W (0 98 kBTU/hr)
Heat Dissipation
Input Service*
Normal Mode
40A
40A
570W (1.95 kBTU/hr)
570W (1 95 kBTU/hr)
Heat Dissipation
Input Service*
Normal Mode
60A
60A
860W (2.93 kBTU/hr)
860W (2 93 kBTU/hr)
Specifications