Powerware 9155 User Manual page 52

Parallel ups 8-15 kva
Hide thumbs Also See for 9155:
Table of Contents

Advertisement

OPERATION
6.
7.
8.
46
EATON Powerware
Configure the UPS for parallel operation through the front panel:
S
Press any button on the front panel display to activate the menu
options.
S
Using the
button, scroll to the Settings menu, and then press
the
button twice to select the User Settings menu.
S
Using the button, scroll to the Parallel Operation Settings
option and press the
S
Press the
button to select the Parallel Unit Number option.
S
Use the button to scroll the Unit number to identify the UPS
number of the parallel system (Unit #1, Unit #2, or Unit #3).
S
Press the
button to save the setting.
S
Use the button to scroll to the Parallel Operation Mode option
and press the
button to enter the menu.
S
Use the button to scroll the desired option (either Redundant
Mode or Capacity Mode).
S
Press the
button to save the setting.
ESC
Press the
button until the Eaton Powerware logo appears.
Repeat Steps 6 and 7 for the remaining UPSs in the parallel system.
®
9155 Parallel UPS (8–15 kVA) User's Guide
button.
S
164201592 Rev C www.powerware.com

Advertisement

Table of Contents
loading

Table of Contents