OPERATION
Table 4. User Settings (continued)
Description
Synchronization Window
Unsynchronized Transfer to Bypass
Output Frequency Slew Rate
Usage of Bypass
Transfer to Bypass When Overload
Automatic Start Delay
Control Commands from X-Slot1
Control Commands from X-Slot2/Serv
X-Slot Signal Input Activation Delay
Input signal delayed shutdown delay
Site Wiring Fault Notice
Reset Custom Event Settings
Auto Output Configuration
44
EATON Powerware
Available Settings
±0.5 through ±3.0 Hz
(0.1 Hz increments)
Allowed/Not Allowed
0.1 though 5 hertz per second
(0.1 Hz increments)
Enabled/Disabled
After a delay/Immediately
-1 through 32767 seconds
(-1 means disabled)
Allowed/Disabled
Allowed/Disabled
0 through 65 seconds
1 through 65535 seconds
Enabled/Disabled
0 through 32
Enabled/Disabled
®
9155 Parallel UPS (8–15 kVA) User's Guide
Default Setting
±2.0 Hz
Not Allowed
0.5 Hz/s
Enabled
After a delay
0s
Allowed
Allowed
5s
120s
Enabled
Total: 0/32
Enabled for initial startup
Disabled after initial startup