Advertisement

A.5
Configuring Smart Meter Using Pushbuttons,
Selecting Engineering
Units
WARNING
Table A-5
Selecting Engineering Units
Step
1
Loosen lock on meter end-cap and unscrew
cap from housing. Be sure transmitter power
is ON.
2
Press UNITS SET button.
3
Press Increase
Decrease
key to call up previous code.
Repeat this action until desired code is on
display.
You can hold down the Increase or Decrease
key to scroll forward or backward through the
codes.
ATTENTION
is configured for SQUARE ROOT output
conformity the only valid code selections are
If transmitter is configured for LINEAR output
conformity EU0 (%) to EUC and EUF
(CUSTOM) are valid code selections.
2/05
The procedure in Table A-5 outlines the steps for selecting the desired
engineering units for a smart meter using its local adjustments on the
face of the meter. You will be selecting the unit of measurement that
you want the smart meter to indicate during normal operation.
When the transmitter's end-cap is removed, the housing is not
explosionproof.
Action
key to call up next code or
Remember that if transmitter
EU0 (%)
EUD (GPM)
EUE (GPH)
EUF (Custom)
ST 3000 Release 300 Installation Guide
Meter Display
Display shows code for current engineering
units setting.
V A R
SEL.
0
%
0
EU
ANALOG
Selection codes for engineering units
VA R
SEL.
%
0
1
EU
ANALOG
Press and hold to
scroll backward
through selections
EU0 = %*
EU1 = inH
EU2 = mmHg*
EU3 = PSI*
EU4 = KPa
EU5 = MPa
EU6 = mbar
EU7 = bar
EU8 = g/cm
EU9 = Kg/cm
EUA = mmH
EUB = inHg
EUC = mH
EUD = GPM*
EUE = GPH*
EUF = Custom
Continued
UPPE R
VALUE
100
UNITS
%
S E T
LOWER
VALUE
UPPE R
VALUE
100
UNIT S
S E T
In H O
LOWER
2
VALUE
Press and hold to
scroll forward
through selections
O*
2
2
2
O
2
O
2
*These selections
have indicators on
the display.
Continued on next page
61