Table 5 Operating Temperature Limits (Transmitters With Silicone Fill Fluids) - Honeywell ST 3000 Installation Manual

Smart transmitter
Hide thumbs Also See for ST 3000:
Table of Contents

Advertisement

3.1
Considerations for ST 3000 Transmitter,
Temperature limits
Table 5
Operating Temperature Limits (Transmitters with Silicone Fill Fluids)
Transmitter Type and Model
Draft Range
STD110
Differential Pressure STD125
STD120, STD130, STD170
STD904, STD924,
STD930, STD974
Gauge Pressure
STG140, STG170, STG180,
STG14L, STG17L, STG18L
STG14T
STG93P
STG944, STG974
STG90L, STG94L,
STG97L, STG98L
Absolute Pressure STA122
STA140
STA922
STA940
Flange Mounted
STF128, STF132, STF924,
STF932
Pseudo-Flanged Head
STF12F, STF13F, STF92F,
STF93F
STF14F
Gauge Pressure Flange Mount
STF14T
Remote Diaphragm Seals
STR12D, STR13D, STR14G,
STR17G, STR14A
STR93D, STR94G
Process temperatures above 125 °C (257 °F) require a reduction in the maximum ambient temperature as follows:
Process Temperature
150 °C (302 °F)
140 °C (284 °F)
125 °C (257 °F)
†† Process temperatures above 65 °C (149 °F) require a 1:1 reduction in maximum ambient temperature.
NOTE: For transmitters with local meter option see Table A-2.
NOTE: Transmitters with other fill fluids (CTFE, Neobee, Etc.) have different Operating Temperature Limits. For
more specific information, refer to the appropriate Specification and Model Selection Guide or transmitter nameplate
18
Table 5 lists the operating temperature limits for the various types of
transmitters with silicone fill fluids. See transmitter specifications for
temperature limits of transmitter with alternative fill fluids.
Ambient Temperature
°C
-40 to 70
-40 to 85
-40 to 93
-40 to 85
-40 to 93
-40 to 93
-15 to 65
-40 to 85
-40 to 85
-40 to 93
-40 to 93
-40 to 85
-40 to 85
-40 to 93
-40 to 93
-40 to 85
-40 to 93
See Specification Sheet
-40 to 85
ST 3000 Release 300 Installation Guide
Process Interface Temperature
°F
-40 to 158
-40 to 185
-40 to 200
-40 to 185
-40 to 200
-40 to 200
5 to 149
-40 to 185
-40 to 185
-40 to 200
-40 to 200
-40 to 185
-40 to 185
-40 to 200
-40 to 200
-40 to 185
-40 to 200
-40 to 150 †
-40 to 185
Ambient Temperature Limit
50 °C (122 °F)
60 °C (140 °F)
85 °C (185 °F)
Continued
°C
°F
-40 to 70
-40 to 158
-40 to 85
-40 to 185
-40 to 125
-40 to 257
-40 to 125
-40 to 257
-40 to 125
-40 to 257
-40 to 150 †
-40 to 302 †
-15 to 95 ††
5 to 203 ††
-40 to 125
-40 to 257
-40 to 110
-40 to 230
See Specification Sheet
-40 to 80
-40 to 176
See Specification Sheet
-40 to 80
-40 to 176
-40 to 175
-40 to 350
-40 to 93
-40 to 200
-40 to 85
-40 to 185
-40 to 302 †
See Specification Sheet
See Specification Sheet
2/05