Table 15 Wiring The Transmitter - Honeywell ST 3000 Installation Manual

Smart transmitter
Hide thumbs Also See for ST 3000:
Table of Contents

Advertisement

4.3
Wiring ST 3000 Transmitter,
Wiring connections
ATTENTION
2/05
The procedure in Table 15 shows the steps for connecting power to the
transmitter. For loop wiring and external wiring diagrams, refer to the
installation drawings presented in Section 5. Detailed drawings are
provided for transmitter installation in non-intrinsically safe areas and
for intrinsically safe loops in hazardous area locations. If you are using
the transmitter with Honeywell's TPS system, see the previous TPS
reference.
• All wiring must comply with local codes, regulations, and
ordinances.
• If you will be using the transmitter in a hazardous area, be sure to
review the hazardous location reference data included in Appendix
A of this manual before operating the transmitter.
Table 15
Wiring the Transmitter
Step
1
Loosen end-cap lock using a 1.5 mm allen wrench and remove end-
cap cover from terminal block end of transmitter housing.
Feed loop power leads through one of conduit entrances on either
2
side of transmitter housing. Plug whichever entrance you do not use.
ATTENTION
Observing polarity, connect positive loop power lead to SIGNAL +
3
terminal and negative loop power lead to SIGNAL – terminal.
Example - Connecting loop power to transmitter.
3-screw terminal block
Loop
Power
+
-
4
Replace end-cap, and tighten end-cap lock.
ST 3000 Release 300 Installation Guide
Continued
Action
The transmitter accepts up to 16 AWG wire.
5-screw terminal (option LP)
Loop
Power
+
-
+
-
+
-
L
+
-
-
+
-
Continued on next page
41