Figure 2 Location Of Failsafe Direction Jumper On Pwa; Table 4 Cutting Failsafe Direction Jumper - Honeywell ST 3000 Installation Manual

Smart transmitter
Hide thumbs Also See for ST 3000:
Table of Contents

Advertisement

2.4
Changing Default Failsafe Direction,
Procedure, continued
Figure 2
Location of Failsafe Direction Jumper on PWA.
Failsafe
Direction
Jumper
14
Table 4
Cutting Failsafe Direction Jumper
Step
With transmitter on bench and no power applied. Loosen end-cap
1
lock and unscrew end cap from electronics side of transmitter
housing.
2
If applicable, unsnap Local Smart Meter from PWA mounting
bracket and unplug cable from connector on back of meter
assembly.
Loosen two retaining screws and carefully pull mounting bracket
and PWA from housing.
Using retaining clip remove flex-tape connector from PWA.
Remove 2-wire power connector from PWA, and then remove
PWA and mounting bracket assembly.
3
With component side of PWA facing you, locate failsafe jumper W1
and cut it in half with small wire cutter such as dykes. See Figure 2.
This changes failsafe action from upscale to downscale.
Reverse applicable previous steps to replace PWA.
4
6
Turn ON transmitter power.
ST 3000 Release 300 Installation Guide
Continued
Action
Power
Connector
Meter
Connector
2/05