Wire Length

Maximum recommended wire lengths for the sensor are given in
Table 1.
Note: The total resistance of these low voltage wires must not exceed 2.5 Ω/conductor. Any resistance greater than 2.5 Ω
BAS-SVX17B-EN
Recommended wire lengths
Wire size
AWG
22
20
18
16
14
may cause the control to malfunction due to an excessive voltage drop.
Maximum recommended wire length from unit
controller to sensor
2
mm
Meters
0.33
0.50
47–73
0.75
74–117
1.30
118–185
2.00
186–296
Pre-Installation
Table
1:
0–46
0–150
151–240
241–385
386–610
611–970
Feet