Scheduling for VAV Occupied Periods

BAS-SVX17B-EN
Cooling setpoint
12. Press
selected
setpoint symbol and the cooling symbol flash. The current
cooling setpoint appears (or dashes if nothing has been set).
13. Press
you are scheduling.
Fan Auto
14. Press
the currently selected fan setting flashes.
Note: CV/HP only, and only if the programmable fan option is enabled.
15. Press
Fan On
scheduling.
To confirm your schedule settings, press
16.
seconds, or wait 30 seconds. The home screen will appear.
Occupancy setting
1. Follow steps 1—8 of the procedure described in
selected
2. Press
Warm-up setpoint
3. Press
selected
4. Press
Supply air heating
5. Press
setpoint selected
6. Press
Supply air cooling
7. Press
setpoint selected
8. Press
9.
to select the cooling setpoint. The top arrow of the
or
to change the cooling setpoint for the period
to select the fan setting. The fan setting appears and
or
to select the fan setting for the period you are
p.
20.
or
to select the occupied setting.
to select the warm-up setpoint. The bottom current
period will flash.
Note: Only if the heat installed option is enabled.
or
to change the setpoint.
to select the supply air heating setpoint. The bottom
arrow of the setpoint symbol, the heating symbol, and the fan
and arrow outlines all flash.
Note: Only if the modulated heat option is enabled.
or
to change the setpoint.
to select the supply air cooling setpoint.The top
arrow of the setpoint symbol, the cooling symbol, and the fan
and arrow outlines all flash.
or
to change the setpoint.
To confirm your schedule settings, press
seconds, or wait 30 seconds. The home screen will appear.
Operation
and hold for 2
"Scheduling, "
and hold for 2