Configuration - Trane X1379088401 Installation, Operation And Maintenance Manual

Programmable zone sensor
Table of Contents

Advertisement

Configuration

The programmable zone sensor is configured by selecting options to determine system and
functional operations.
The sensor can be configured to operate with one of the following units:
The functional options that are available depend on whether the sensor is configured for a CV, an
HP , or a VAV unit.
To configure the sensor:
1. Press and hold the Test/Configuration button for 2 seconds
Figure 4. Pressing the Test/Configuration button
2. Use the keypad on the sensor cover to select the system and functional options. See
3. To confirm the selection and return the display to the home screen, either:
BAS-SVX17B-EN
A constant-volume (CV) unit
A heat pump (HP) unit
A variable-air-volume (VAV) unit
appears (see
Figure 3, p.
Keypad
Test/Configuration button
p. 14
for sensors used with CV or HP units; see
Press
,
, or
Press
or
to change the option value.
Press the Test/Configuration button, or
Press and hold
Note: The sensor will revert to the home screen if no buttons are pressed for 90 seconds.
12).
Table 4, p.
to change the option number.
for 2 seconds
(Figure
4). The configuration screen
16, for sensors used with VAV units.
Table 3,
13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents