General Information; Product Description - Trane X1379088401 Installation, Operation And Maintenance Manual

Programmable zone sensor
Table of Contents

Advertisement

General Information

This section provides a description of the sensors, as well as part numbers and dimensions.

Product Description

The Trane
IntelliPak control units. It has the following features:
4
®
programmable zone sensor (p/n X1379088401) can be used with UCP , Reliatel, and
A liquid crystal display (LCD) with symbols for zone temperature, temperature setpoints,
system operating modes, day of the week, time of day, and occupancy settings
Configurable to operate with constant-volume (CV) units, heat pump (HP) units, and variable-
air-volume (VAV) units
System modes:
– CV: Heat, Cool, Auto, Off
– HP: Emergency Heat, Heat, Cool, Auto, Off
– VAV: Auto, Off
A cooling setpoint range (occupied) of 45ºF to 98ºF (7.2ºC to 36.7ºC)
A heating setpoint range (occupied) of 43ºF to 96ºF (6.1ºC to 35.6ºC)
Two fan modes (CV and HP only): On, Auto
A table of configurable functional options (see
Scheduling function: 7 days per week and up to 4 periods per day, occupied/unoccupied mode
Temporary override function
During occupied periods, an auxiliary relay rated for 1.25 A @ 30 Vac with one set of single-pole
double-throw contacts is activated.
Table 3, p. 14
and
Table 4, p.
16)
BAS-SVX17B-EN