Configuration
Table 3.
Configuration options for sensors used with
Option
number
Function
0
Operation mode
(See Note)
1
Morning warm-up
Economizer minimum
2
position override during
unoccupied period
3
Temperature scale
4
Supply air tempering
5
Time clock
6
Smart fan
7
Computed recovery
Programmable days per
8
week
Programmable periods
9
per day
Programmable fan
10
operation
11
Remote sensor installed
12
Check filter interval
14
constant-volume (CV)
Option value
0 = Constant-volume (CV)
1 = Heat pump (HP)
2 = Variable-air-volume (VAV)
0 = Disabled
1 = Enabled
0 = Disabled
1 = Enabled
0 = ºF
1 = ºF + 0.5
2 = ºF + 0.1
3 = ºC
4 = ºC + 0.5
5 = ºC + 0.1
0 = Disabled
1 = Enabled
0 = 12 hour
1 = 24 hour
0 = Disabled
1 = Enabled
0 = Disabled
1 = Enabled
0 = 7 days (M, T, W, Th, F, S, S)
1 = 5 +1 days (M–F, S, S)
2 = 5 + 2 days (M–F, S–S)
3 = 1 day
2 = Day and Night
3 = Morning, Day, Night
4 = Morning, Day, Evening,
Night
0 = Disabled
1 = Enabled
0 = No
1 = Yes
0 = Disabled
1–199 = Number of 1-day
increments
or
heat pump (HP)
Default Description
Configures the operation mode of the sensor.
Note: To access option number 0, with the configuration
0
screen showing, press the up and down arrows
simultaneously for 2 seconds. Option number 0 will
appear on the display.
If enabled, the heat turns on when the program switches
from unoccupied to occupied and the zone temperature is
0
2ºF (1.1ºC) below the heating setpoint temperature. The
heat terminates after 60 minutes regardless of whether
the setpoint has been reached.
If enabled, the minimum position of the economizer
1
damper is overridden during the unoccupied period.
0
Displays the temperature in the selected format.
If enabled, this setting sends the tempering signal to the
0
UCP.
• 0 sets clock to 12-hour format with AM and PM.
0
• 1 sets clock to 24-hour military time.
If enabled, the supply fan operates in the Auto mode
1
during unoccupied periods, regardless of the fan setting.
If enabled, this option offsets the setpoint temperature
and starts the system before the scheduled occupied
period to efficiently reach the occupied temperature
0
setpoint. The time is calculated based on a recovery rate
of 6ºF (3.3ºC) per hour. If configured for an HP unit, option
7 is disabled for emergency heat operation.
• If 0 is selected, all 7 days to be programmed differently.
• If 1 is selected, week days, Sat, and Sun can be
programmed differently from one another.
0
• If 2 is selected, week days can be programmed one way
and Sat-Sun can be programmed another way.
• If 3 is selected, all seven days are limited to being
programmed the same way.
• If 2 is selected, only Day and Night periods can be
programmed.
• If 3 is selected, only Morning, Day, and Night periods can
4
be programmed.
• If 4 is selected, Morning, Day, Evening, and Night
periods can be programmed.
If enabled, the supply fan operation can be programmed
0
for On or Auto operation for each programmed period.
If Yes is selected, the space temperature of the remote
0
sensor will appear on the display and will be communicated
to the unit controller.
Adjustable in 1-day increments. The check filter symbol
30
flashes when the accumulated run time is greater than the
programmed setting.
units
BAS-SVX17B-EN