Trane X1379088401 Installation, Operation And Maintenance Manual page 16

Programmable zone sensor
Table of Contents

Advertisement

Configuration
Table 4.
Configuration options for sensors used with
Option
number
Function
0
Operation mode
(See Note)
1
Morning warm-up
Economizer minimum
2
position override during
unoccupied period
3
Temperature scale
4
Heat installed
5
Time Clock
6
Modulated heat
7
Daytime warm-up
Programmable days per
8
week
Programmable periods
9
per day
10
Remote sensor installed
11
Check filter interval
Display zone
12
temperature
13
Keypad lockout
16
variable-air-volume (VAV)
Option Value
0 = Constant-volume (CV)
1 = Heat pump (HP)
2 = Variable-air-volume (VAV)
0 = Disabled
1 = Enabled
0 = Disabled
1 = Enabled
0 = ºF
1 = ºF + 0.5
2 = ºF + 0.1
3 = ºC
4 = ºC + 0.5
5 = ºC + 0.1
0 = No
1 = Yes
0 = 12 hour
1 = 24 hour
0 = No
1 = Yes
0 = Disabled
1 = Enabled
0 = 7 days (M, T, W, Th, F, S, S)
1 = 5 +1 days (M–F, S, S)
2 = 5 + 2 days (M–F, S–S)
3 = 1 day
2 = Day and Night
3 = Morning, Day, Night
4 = Morning, Day, Evening,
Night
0 = No
1 = Yes
0 = Disabled
1–199 = Number of 1-day
increments
0 = No
1 = Yes
0 = Disabled
1 = Enabled
units
Default
Description
Configures the operation mode of the sensor.
Note: To access option number 0, with the configuration
0
screen showing, press the up and down arrows
simultaneously for 2 seconds. Option number 0 will
appear on the display.
If enabled, the heat turns on when the program switches
0
from unoccupied to occupied and the zone temperature is
1.5ºF (0.8ºC) below the warm-up setpoint temperature.
If enabled, the minimum position of the economizer
1
damper is overridden during the unoccupied period.
0
Displays the temperature in the selected format.
Allows the warm-up setpoint to be programmed during
0
occupied periods.
• 0 sets clock to 12-hour format with AM and PM.
0
• 1 sets clock to 24-hour military time.
The modulated heat is controlled to the supply air heating
0
setpoint.
If enabled, this setting allows the system to automatically
0
switch between supply air cooling and constant-volume
heating operation during an occupied period.
• If 0 is selected, all 7 days to be programmed differently.
• If 1 is selected, week days, Sat, and Sun can be
programmed differently from one another.
0
• If 2 is selected, week days can be programmed one way
and Sat-Sun can be programmed another way.
• If 3 is selected, all seven days are limited to being
programmed the same way.
• If 2 is selected, only Day and Night periods can be
programmed.
• If 3 is selected, only Morning, Day, and Night periods can
4
be programmed.
• If 4 is selected, Morning, Day, Evening, and Night
periods can be programmed.
If yes is selected, the space temperature of the remote
0
sensor will appear on the display and will be
communicated to the unit controller.
Adjustable in 1-day increments. The check filter symbol
30
flashes when the accumulated run time is greater than the
programmed setting.
If sensor is in a normal running state or in temporary
1
occupancy (timed override), the zone temperature
appears.
1
If enabled, the keypad can be locked out.
BAS-SVX17B-EN