Programmable zone sensor
Table of Contents

Advertisement

Table 3.
Configuration options for sensors used with
Option
number
Function
Display zone
13
temperature
14
Keypad lockout
Default temporary
15
override timer setting
Zone temperature
16
calibration
17
Baud rate
18
Default cooling setpoint
19
Default heating setpoint
Minimum cooling
20
setpoint
Maximum heating
21
setpoint
Minimum setpoint
22
deadband
BAS-SVX17B-EN
constant-volume (CV)
Option value
0 = No
1 = Yes
0 = Disabled
1 = Enabled
1, 2, 3, 4, 5 (hours)
Displays current temperature
reading with any offsets:
• 1 = –9.9ºF (–5.5ºC)
• 100 = 0.0ºF (0.0ºC)
• 199 = 9.9ºF (9.9ºC)
0 = 1024 baud
1=1200 baud
45–98ºF (7.2–36.7ºC)
43–96ºF (6.1–35.6ºC)
45–98ºF (7.2–36.7ºC)
43–96ºF (6.1–35.6ºC))
0 = 2ºF (1ºC)
1 = 4ºF (2ºC)
2 = 5ºF (3ºC)
3 = 7ºF (4ºC)
4 = 8ºF (5ºC)
5 = 10ºF (6ºC)
or
heat pump (HP)
Default Description
If the sensor is in a normal running state or in temporary
1
occupancy (timed override), the zone temperature
appears.
1
If enabled, the keypad can be locked out.
3
Sets the default temporary override time in hours.
Allows for field calibration in 0.1ºF (0.6ºC) increments of
either the internal sensor on the sensor, or the remote
100
sensor if used.
(0
offset)
Important: Apply power to the sensor for 60 minutes before
calibrating.
Set to 0 for 3–25 ton Voyager units built before January 1,
1
1996, that have the original UCP.
If no setpoint has been programmed or the program is lost,
74
the value that is set becomes the operation setpoint.
If no setpoint has been programmed or the program is lost,
68
the value that is set becomes the operation setpoint.
Sets the minimum programmable cooling temperature
45
setpoint.
Sets the maximum programmable heating temperature
96
setpoint.
Sets the minimum difference between the heating and
0
cooling setpoints.
Configuration
units (continued)
15