Alarm Signal - Hitachi SJ100 Instruction Manual

Sj100 series
Hide thumbs Also See for SJ100:
Table of Contents

Advertisement

4–30
Using Intelligent Output Terminals

Alarm Signal

The inverter alarm signal is active when a fault has
occurred and it is in the Trip Mode (refer to the
diagram at right). When the fault is cleared the
alarm signal becomes inactive.
We must make a distinction between the alarm
signal AL and the alarm relay contacts [AL0],
[AL1] and [AL2]. The signal AL is a logic
function, which you can assign to the open collec-
tor output terminals [11] or [12] or the relay
outputs. The most common (and default) use of the relay is for AL, thus the labeling of
its terminals. Use an open collector output (terminal [11] or [12]) for a low-current logic
signal interface or to energize a small relay (50 mA maximum). Use the relay output to
interface to higher voltage and current devices (10 mA minimum).
Option
Terminal
Code
Symbol
05
AL
Valid for outputs:
Required settings:
Notes:
When the alarm output is set to normally closed, a
time delay of less than 2 seconds occurs until the
contact is closed when the power is turned ON.
Terminals [11] and [12] are open collector outputs,
so the electric specifications of [AL] are different
from the contact output terminals [AL0], [AL1],
[AL2].
When the inverter power supply is turned OFF, the
alarm signal output is valid as long as the external
control circuit has power.
This signal output has the delay time (300 ms
nominal) from the fault alarm output.
The relay contact specifications are in
tions of Control and Logic Connections" on
page
4–6. The contact diagrams for different condi-
tions are on the next page.
Output
Function Name
State
Alarm Signal
ON
OFF
11, 12, AL0 – AL2
C_24, C_33
"Specifica-
Run
Fault
Description
when an alarm signal has occurred and has not
been cleared
when no alarm has occurred since the last
clearing of alarm(s)
Example for terminal [11] or [12] (requires
output configuration—see page 3–38):
Inverter output
terminal circuit
H O OI
L
FM CM2
+
Example for terminals [AL0], [AL1], [AL2]
(default output configuration shown—
see page 3–38):
Inverter logic
circuit board
Relay position
shown is during
normal running
AL0
(no alarm).
Power
See I/O specs
supply
on page 4–6.
STOP
RESET
Stop
RUN
STOP
RESET
Trip
Fault
Alarm signal active
AL
12 11
RY
AL
AL1
AL2
Load

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents