Using Intelligent Output Terminals
Frequency Arrival Signals
The Frequency Arrival group of outputs help coordinate external systems with the
current velocity profile of the inverter. As the name implies, output [FA1] turns ON
when the output frequency arrives at the standard set frequency (parameter F_01).
Output [FA2] relies on programmable accel/ decel thresholds for increased flexibility.
For example, you can have an output turn ON at one frequency during acceleration, and
have it turn OFF at a different frequency during deceleration. All transitions have hyster-
esis to avoid output chatter if the output frequency is near one of the thresholds.
Option
Terminal
Code
Symbol
01
FA1
02
FA2
Valid for outputs:
Required settings:
Notes:
For most applications you will need to use only one
type of frequency arrival outputs (see examples).
However, it is possible assign both output terminals
to output functions [FA1] and [FA2].
For each frequency arrival threshold, the output
anticipates the threshold (turns ON early) by 1.5Hz.
The output turns OFF as the output frequency
moves away from the threshold, delayed by 0.5Hz.
The delay time of the output signal is 60 ms
(nominal).
NOTE: The example circuit in the table above drives a relay coil. Note the use of a diode
to prevent the negative-going turn-off spike generated by the coil from damaging the
inverter's output transistor.
Output
Function Name
State
Frequency Arrival
ON
Type 1 – Constant
OFF
Speed
Frequency Arrival
ON
Type 2 – Over-
frequency
OFF
11, 12, AL0 – AL2
(none)
Description
when output to motor is at the set frequency
when output to motor is OFF, or in any accelera-
tion or deceleration ramp
when output to motor is at or above the set
frequency thresholds for, even if in acceleration
or deceleration ramps
when output to motor is OFF, or during accelera-
tion or deceleration before the respective thresh-
olds are crossed
Example (default output configuration
shown—see page 3–38):
Inverter output
terminal circuit
H O OI
L
See I/O specs
on page 4–6.
FA1
FM CM2
12 11
+
RY