Alarm Signal - Hitachi WJ200 Series Quick Reference Manual

Wj200 series inverter single-phase input 200v class three-phase input 200v class three-phase input 400v class
Hide thumbs Also See for WJ200 Series:
Table of Contents

Advertisement

CALL NOW 800-985-6929

Alarm Signal

The inverter alarm signal is active when a fault has
occurred and it is in the Trip Mode (refer to the
diagram at right). When the fault is cleared the alarm
signal becomes inactive.
We must make a distinction between the alarm signal
AL and the alarm relay contacts [AL0], [AL1] and [AL2].
The signal AL is a logic function, which you can assign
to the open collector output terminals [11], [12], or the
relay outputs.
The most common (and default) use of the relay is for AL, thus the labeling of its terminals.
Use an open collector output (terminal [11] or [12]) for a low-current logic signal interface
or to energize a small relay (50 mA maximum). Use the relay output to interface to higher
voltage and current devices (10 mA minimum).
Option
Code
05
Valid for inputs:
Required settings
Notes:
By default, the relay is configured as normally
closed (C036=01). Refer to the next page for an
explanation.
In the default relay configuration, an inverter
power loss turns ON the alarm output. the alarm
signal remains ON as long as the external control
circuit has power.
When the relay output is set to normally
closed, a time delay of less than 2 seconds occurs
after powerup before the contact is closed.
Terminals [11] and [12] are open collector
outputs, so the electric specifications of [AL] are
different from the contact output terminals [AL0],
[AL1], [AL2].
This signal output has the delay time (300 ms
nominal) from the fault alarm output.
The relay contact specifications are in
Logic Signal Specifications" on page 4–6.
contact diagrams for different conditions are on
the next page.
CALL NOW 800-985-6929
http://www.automatedpt.com
Terminal
Function Name
Symbol
AL
Alarm Signal
11, 12, AL0 – AL2
C031, C032,
C036
http://www.automatedpt.com
Fault
State
ON
when an alarm signal has occurred and has not
been cleared
OFF
when no alarm has occurred since the last clearing
of alarm(s)
Example for terminal [11] (default output
configuration shown – see
Inverter output
terminal circuit
Example for terminal [AL0], [AL1], [AL2] (requires
output configuration – see
Inverter logic
circuit board
"Control
The
See I/O specs on
39
Email: charles@automatedpt.com
STOP
RESET
Run
Stop
RUN
STOP
RESET
Trip
Fault
Alarm signal active
Description
page
3-54):
AL
CM2
11
RY
page 4-35 and
3-54):
AL
AL0
AL1
AL2
Power
Load
supply
page 4-6
Email: charles@automatedpt.com

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents