3–42
"C" Group: Intelligent Terminal Functions
Func.
Name /
Code
SRW Display
C_43 Arrival frequency
setting for deceleration
ARV DEC
C_44 PID deviation level
setting
OV PID
C_81 O input span calibration Scale factor between the
ADJ-O
C_82 OI input span calibra-
tion
ADJ-OI
C_91 Debug mode enable
INIT DEBG
C_92 Core monitor address
(not displayed)
C_93 Core monitor date
(not displayed)
C_94 Core set address
(not displayed)
C_95 Core set date
(not displayed)
NOTE: Settings C_81 and C_82 are factory-calibrated for each inverter. Do not change
these settings unless absolutely necessary. Note that if you restore factory defaults for all
parameters, these settings will not change.
"C" Function
Description
Sets the frequency arrival
setting threshold for the output
frequency during deceleration
000.0Hz
Sets the allowable PID loop
error magnitude (absolute
value), SP - PV, range is 0.0 to
003.0%
100%, resolution is 0.1%
external frequency command
082
on terminals L – O (voltage
input) and the frequency output
Scale factor between the
external frequency command
on terminals L – OI (current
066
input) and the frequency output
(Reserved) DO NOT EDIT
OFF
(Reserved) DO NOT EDIT
(Reserved) DO NOT EDIT
(Reserved) DO NOT EDIT
(Reserved) DO NOT EDIT
Defaults
Run
Mode
–FE
–FU
–FR
Edit
(CE)
(UL)
(Jpn)
0.0
0.0
3.0
3.0
Factory-calibrated
Factory-calibrated
00
00
0000
0000
0000
D_01 D_01 D_01
00
00
Units
0.0
Hz
3.0
%
00
00