Hitachi SJ100 Instruction Manual page 175

Sj100 series
Hide thumbs Also See for SJ100:
Table of Contents

Advertisement

6–6
Monitoring Trip Events, History, & Conditions
Error
Code
E 1 0
E 1 1
E 2 2
E 1 2
E 1 3
E 1 4
E 1 5
E 2 1
E 3 5
- - -
NOTE: If an EEPROM error (E08) occurs, be sure to confirm the parameter data values
are still correct. If the power is turned OFF while the [RS] (Reset) intelligent input
terminal is ON, an EEPROM error will occur when power is restored.
Name
CT (current transformer)
error
CPU error
External trip
USP
Ground fault
Input over-voltage
Inverter thermal trip
Thermistor
Under-voltage (brown-
out) with output shutoff
Cause(s)
If a strong source of electrical interference is close to
the inverter or a fault occurs in a built-in CT (current
transformer), the inverter trips and turns its output
OFF.
A malfunction in the built-in CPU has occurred, so
the inverter trips and turns OFF its output to the
motor.
A signal on an intelligent input terminal configured as
EXT has occurred. The inverter trips and turns OFF
the output to the motor.
When the Unattended Start Protection (USP) is
enabled, an error occurred when power is applied
while a Run signal is present. The inverter trips and
does not go into Run Mode until the error is cleared.
The inverter is protected by the detection of ground
faults between the inverter output and the motor upon
during powerup tests. This feature protects the
inverter, and does not protect humans.
When the input voltage is higher than the specified
value, it is detected 100 seconds after powerup and
the inverter trips and turns OFF its output.
When the inverter internal temperature is above the
threshold, the thermal sensor in the inverter module
detects the excessive temperature of the power
devices and trips, turning the inverter output OFF.
When a thermistor is connected to terminals [5] and
[L] and the inverter has sensed the temperature is too
high, the inverter trips and turns OFF the output.
Due to low input voltage, the inverter turns its output
OFF and tries to restart. If it fails to restart, then the
alarm trips to record the under-voltage error event.