10-2 Reading setting data from USB memory

To read setting data from USB memory, insert USB to USB port. Touch [Maintenance] on setting change and then touch [Data Utility] tab
to show the screen below.
First, create [SetupData] folder in the root folder of the USB memory using PC. Save the setting data in the [SetupData] folder.
Note: Do not change the file name from that of when backup was performed.
Note: If the folder name or file name is different from the given name, no data can be read.
Note: Check that normal communication between the AG-150A and Expansion controller is established before reading in data from the
USB drive.
Note: If the data is not read, check the folder name and the file name.
Note: If the data is not read, check if the USB memory is inserted correctly.
Note: Do not read the data that was saved from the Expansion controller (PAC-YG50ECA) or GB-50ADA-A, GB-50ADA-J.
Read from USB memory
button
After saving the setting file in the [SetupData] folder, touch [Initial
Setting] or [User Info], and then touch [Read from USB Memory]
button.
Wait for a while. The message "The data has been read" will be
shown when the reading is completed. Check if the selected data was
read correctly.