Mitsubishi Electric AG-150A Instruction Book page 65

Air-conditioner control system centralized controller
Hide thumbs Also See for AG-150A:
Table of Contents

Advertisement

(2) Touch the Interlocked indoor unit button to bring up the interlocked indoor unit selection screen, and touch the number assigned to
the unit to register. An orange frame will appear around the selected items. Touch again to deselect the selected items. Touch again
to deselect the selected item (no orange frame). Press the [OK] button to save the changes, or touch the [Cancel] button to go back
to the previous screen without saving any changes.
Note: A maximum of 16 indoor units can be registered to operate with one ventilator.
(3) Press the [Save setting] on the LOSSNAY interlock setting screen to save the settings.
* When changes are made to the settings, it will take a few minutes for the screen to return to the Main menu.
• Making the interlock settings for a system with connection to an Expansion controller
(PAC-YG50ECA)
To interlock the ON/OFF operation of the LOSSNAY units with the indoor units, from the menu bar on the Setting change screen, touch
[Initial Settings] > [Interlock] and open the LOSSNAY interlock settings screen. , Select the tab that corresponds to the EC controller
whose settings are to be made, and enter the interlock setting conditions.
Note: If the user logs in as a building manager, the operations may be prohibited.
Note: Units that are connected to different Expansion controllers cannot be interlocked with each other.
CAUTION
Be sure to make the settings while the Expansion controller is connected. (Those settings made without the connection of an
Expansion controller will not be reflected.)
LOSSNAY
button
Refer to P 63 for the details of how to make the interlock settings for the LOSSNAY and indoor units.
– 64 –
Interlocked indoor
unit button
Save Settings