Toshiba TOSVERT VF-AS1 Instruction Manual page 89

The new high-performance inverter tosvert
Hide thumbs Also See for TOSVERT VF-AS1:
Table of Contents

Advertisement

Setting of motor electronic thermal protection level 1
If the capacity of the motor is smaller than the capacity of the inverter, or the rated current of the motor is smaller
than the rated current of the inverter, adjust the electronic thermal protection level 1
rated current.
* If the indications are in percentages[%], then 100% equals the inverter's rated output current [A].
Output current reduction factor [%]/[A]
Setting the motor overload starting level
2) Motor 150%-overload time limit
The motor 150%-overload time limit parameter
a load of 150% (overload trip
Operation frequency
0.01Hz *1
Motor overload
time [s]
Motor 150%-
overload time limit
0
×0.6
[Parameter setting]
Title
Motor 150%-overload time limit
×1.0
×0.6
0
=
is used to set the time elapsed before the motor trips under
) within a range of 10 to 2400 sec.
[Example setting]
Operation
Monitored output
frequency
current [%]
no less than
=
68
70
80
90
100
112
120
130
140
150
200
×1.1
×1.5
Motor overload protection characteristics
Function
E-23
so that it fits the motor's
Hz
Output frequency [Hz]
Motor overload time [s] (Outline data)
=
=
0.01Hz
34
7200
35
3600
40
1000
45
600
50
420
56
12000
310
60
2400
270
65
1200
230
70
800
190
75
600
170
100
270
110
Monitored output current [%]
*1 Except for the cases of
Adjustment range
~
sec.
E6581301
5
=
0.01Hz
3600
1800
500
300
210
6000
155
1200
135
600
115
400
95
300
85
135
55
=
[Hz]
,
Default setting

Advertisement

Table of Contents
loading

Table of Contents