Error
code
*
*
13
*
*Presence or absence of parameter trip can be selected.
(Continued overleaf)
Description
Possible causes
•The V/f parameter is improperly set.
•The motor is locked up.
•Low-speed operation is performed
Motor overload
continuously.
•An excessive load is applied to the
motor during operation.
•Rapid deceleration is operated.
Dynamic
•Dynamic braking is too large.
braking resistor
overload
•The input voltage fluctuates abnormally.
(1)The power supply has a capacity
of 500kVA or more.
(2)A power factor improvement
Overvoltage
capacitor is opened and closed.
during
(3)A system using a thyrister is
acceleration
connected to the same power
distribution line.
•A restart signal is input to the
rotating motor after a momentary
stop, etc.
•The deceleration time
short (regenerative energy is too
large).
•The dynamic braking resistor has a
considerably large resistance.
(Dynamic braking resistor) is OFF.
Overvoltage limit operation
Overvoltage
is OFF.
during
•The input voltage fluctuates abnormally.
deceleration
(1)The power supply has a capacity
of 500kVA or more.
(2)A power factor improvement
capacitor is opened and closed.
(3)A system using a thyrister is
connected to the same power
distribution line.
•The input voltage fluctuates
abnormally.
(1)The power supply has a capacity
of 500kVA or more.
(2)A power factor improvement
Overvoltage
capacitor is opened and closed.
during fixed
(3)A system using a thyrister is
speed operation
connected to the same power
distribution line.
•The motor is in a regenerative
state because the load causes the
motor to run at a frequency higher
than the inverter output frequency.
•Overtorque reaches to a detection
level during operation.
•Stall prevention operation was
Overtorque
performed continuously for a
length of time longer than that set
with
•The output current decreased to a
Low current
low-current detection level during
operation
operation.
•The input voltage (in the main
circuit) is too low.
Undervoltage
•Momentary power failure occurs
(main circuit)
because undervoltage continues
longer than undervoltage detection
time
•Inverter is stopped by panel
operation during automatic or
remote operation.
Emergency stop
•A stop command (input terminal
function:
an external control device.
•Check the V/f parameter setting.
•Check the load (operated machine).
•Adjust
withstand during operation in a low speed range.
• Reduce the DC braking amount
DC braking time
•Increase the deceleration time
•Increase the capacity of dynamic braking resistor
(wattage) and adjust PBR capacity parameter
•Insert a suitable input reactor.
•Use
power ride-though control).
is too
•Increase the deceleration time
•Install a dynamic braking resistor.
•Decrease dynamic braking resistance. (Also reset
the
•Set dynamic braking mode parameter
properly.
•Set overvoltage limit operation
•Insert a suitable input reactor.
•Insert a suitable input reactor.
•Install a dynamic braking resistor.
•Check system error.
• Check whether the motor is overloaded or the
brake is engaged.
.
•Check the suitable detection level for the system
(
•Make a service call if the setting is correct.
•Check the input voltage.
•To cope with a momentary stop due to
undervoltage, enable
ride-through control),
and
.
•Reset the inverter.
or
) is issued by
M-2
Remedies
to the overload that the motor can
.
.
.
(Auto-restart) and
(Regenerative
.
.)
).
(Regenerative power
(auto-restart control),
(Undervoltage detection time).
E6581301
and the
properly.