Torque Limit; Torque Limit Switching - Toshiba TOSVERT VF-AS1 Instruction Manual

The new high-performance inverter tosvert
Hide thumbs Also See for TOSVERT VF-AS1:
Table of Contents

Advertisement

6.25

Torque limit

6.25.1 Torque limit switching

• Function
This function is to decrease or increase the output frequency according to the loading condition when the
motor torque reaches the limit level. Setting a torque limit parameter at 250% means "Invalid."
6
Setting methods
(1) When setting limits to torque, use internal parameters (Torque limits can also be set with an external control
device.)
Torque limits can be set with the parameters
[Setting of power running torque]
[Setting of regenerative torque]
: Power running torque limit 1
selection
: Power running torque limit 1
level
: Regenerative braking torque
limit 1 selection
: Regenerative braking torque
limit 1 level
: Power running torque limit 2
level
: Regenerative braking torque
limit 2 level
Regenerative
Reverse run
Power
running
(Power running torque limit 1 selection)
(Power running torque limit 1)
(Regenerative braking torque limit 1 selection) : Set at
(Regenerative braking torque limit 1)
: Power running torque limit 3
level
: Regenerative braking torque
limit 3 level
: Power running torque limit 4
level
: Regenerative braking torque
limit 4 level
Positive torque
Power
running
Regenerative
Negative torque
and
.
: Set at
(
: Set a desirable torque limit level.
(
: Set a desirable torque limit level.
F-42
E6581301
+250% torque
Forward run
-250% torque
)
)