fa51 : 0x2A51(Analog output (FM) data from communication)
7.1.6.
fa52 : 0x2A52(Terminal AM output data) (Only for the VF-AS3)
7.1.7.
Use this function, set the Terminal FM function (fmsl) or Terminal AM function (f670) to
communication data output (18 for VF-S15 / 31 for VF-AS3).
It possible to send out the data specified as FM/AM analog output data (fa51/fa52) though the
FM/AM analog output terminal. Data can be adjusted in a range of 0 to 100.0% (resolution of 10 bit).
Please refer to "Meter setting and adjustment" Section of the VF-S15/MB1 instruction manual for details.
Please refer to "Adjusting the meter connected to the inverter" Section of the VF-AS3 instruction manual
for more details.
7.1.8.
f441
: 0x2441
7.1.9.
f443
: 0x2443
Torque limit level is set up by 0.01% unit and the hexadecimal number.
For example: when "Torque limit level " is set up to "250%", since the minimum unit is 0.01%,
250%=250÷0.01=25000=0x61A8
f460 : 0x2460 (Speed control response 1)(Only for the VF-AS3)
7.1.10.
Speed control response is set up by 0.01% unit and the hexadecimal number.
For example: when "Speed control response " is set up to "1.0%", since the minimum unit is 0.1%,
1%=1÷0.1=10=0x000A
7.1.11.
f461 : 0x2461 (Speed control stabilization coefficient 1)(Only for the
VF-AS3)
Speed control stabilization coefficient is set up by 0.01% unit and the hexadecimal number.
For example: when "Speed control stabilization coefficient " is set up to "1.00%", since the minimum unit
is 0.01%,
1%=1÷0.01=100=0x0064
(Power running torque limit level 1)(Only for the VF-AS3)
(Regenerative torque limit level 1)(Only for the VF-AS3)
- 33 -