Panasonic WJ-FS616 Operating Instruction page 15

Video multiplexer
Hide thumbs Also See for WJ-FS616:
Table of Contents

Advertisement

Dip Switch Setting
Alarm Output Setting
1. Disassemble the video multiplexer as described for
installing the Data Multiplex Boards on page 11.
VTR
O.C
SW5
SW3
SW4
VTR
O.C
VTR
O.C
2. Set switches (SW3/SW4/SW5) on the board to
choose the alarm control signals as either Open
Collector (O.C) or Pulse (VTR).
Open Collector (O.C): 16V DC 100 mA max.
Pulse (VTR): +5V DC approx. 500 ms
The above switch positions are the initial factory
settings.
SW3 : Alarm Output
SW4 : Alarm Reset Output
SW5 : Alarm & SW Output
Dummy Black Burst Setting
According to the initial factory setting, the Dummy
Black Burst signal is supplied to the REC OUT con-
nector as needed to overwrite any picture dis-
played by error. If this function is not required, set
the switch SW1 to the position shown below.
1. Disassemble the video multiplexer as described for
installing the Data Multiplex Boards on page 11.
OFF
2. Set switch (SW1) on the board to the position
shown above.
-13-
SW1
SW1 : Record Output