Installation
Fireplace Placement Requirements
Minimum Framing Dimensions
The 1/2" stand-offs along the sides and back, and the 2-1/2" stand-offs on top of the fireplace
separate the fireplace from combustible materials (e.g.: combustible framing members, plywood,
sheetrock, paper-backed insulation). The stand-offs may contact the framing members but no material
may be placed between the stand-offs.
This fireplace may be placed in a bedroom. Please be aware of the large amount of heat this appliance
produces when determining a location.
42" Min.
The fireplace enclosure
must not be less than
42" above the base of
the fireplace.
If using a remote
control or thermostat,
route the wire to a
location near the gas
line (include an extra 3'
length for hookup).
Route the electrical line to a
position at the left front of
the fireplace.
•
Fireplace must be installed on a level surface capable of supporting the fireplace and vent
•
Fireplace must be placed directly on wood or non-combustible surface (not on linoleum or carpet)
•
Due to the high temperature of the fireplace, it should be located out of traffic and away from furniture
and draperies.
Clearances
•
When installed, walls in front of the fireplace must be a minimum 8-1/2" to the side of the fireplace
facing (drywall standoff).
•
Fireplace must be placed so that no combustibles are within, or can swing within 36" of the front of the
fireplace (e.g. drapes, doors)
•
Fireplace must be placed so the vents below and above the glass do not become blocked
Travis Industries
(for qualified installers only)
32"
16-7/8"
39-7/8"
9 3 5 0 8 1 1 6
With an elbow directly off the top of the
fireplace, the vent is centerd 36" above
the base of the fireplace.
Wall Thimble (required when
passing through a wall)
Gas line (3/8" M.P.T. or 1/2" F.P.T.)
should be routed 4-1/2" behind the
framing opening and 3-1/4" above the
base of the fireplace on the right side
(see "Gas Line Connection" for
details).
0 3 1 0 0 0
7