Installation
16

Vent Requirements

!
The vent must maintain the required clearance to combustible materials to prevent a fire (see
"Clearances" below). Do not fill air spaces with insulation.
!
The gas appliance and vent system must be vented directly to the outside of the building, and never
be attached to a chimney serving a separate solid fuel or gas-burning appliance. Each direct vent gas
appliance must use it's own separate vent system.

Altitude Considerations

This fireplace has been tested at altitudes ranging from sea level to 8,000 feet (2,400 M). In this testing we have
found that the fireplace, with its standard orifice, burns correctly with just an air shutter adjustment.
!
Failure to adjust the air shutter properly may lead to improper combustion which can create a safety hazard.
Consult your dealer or installer if you suspect an improperly adjusted air shutter.

Clearances

Clearance
1" Clearance

Vent Part Numbers

Use Model GS Direct Vent manufactured by Simpson Dura-Vent only . Follow the installation
instructions included with the vent. For the nearest Simpson Dura-Vent supplier, call (800) 835-4429.
Vent part numbers and descriptions are listed below.
Straight Lengths
908B
6" Pipe Length, Black (interior)
907B
9" Pipe Length, Black (interior)
906
12" Pipe Length, Galvanized
906B
12" Pipe Length, Black (interior)
904
24" Pipe Length, Galvanized
904B
24" Pipe Length, Black (interior)
903
36" Pipe Length, Galvanized
903B
36" Pipe Length, Black (interior)
902
48" Pipe Length, Galvanized
902B
48" Pipe Length, Black (interior)
911B
11" to 14 5/8" Adjustable, Black (interior)
Travis Industries
2-1/2"
1"
When using an elbow directly off the top of the fireplace, the
Clearance
following requirements apply:
• A wall thimble is required when the vent passes through the
• Minimum 2-1/2" clearance above the vent before the wall
• Mimimum 1" clearance (in all directions) to the vent after the
With vertical vent (or a 45° offset) directly off th top of the
fireplace, the following requirements apply:
• Firestops or other non-combustible means of support may
• Mimimum 1" clearance (in all directions) to the vent.
(for qualified installers only)
first wall (frame 9" tall by 10" wide).
thimble (1" clearance to the sides and bottom of the vent).
thimble.
be used when passing through a wall
Vent Terminations
981
Snorkel Termination (36" rise)
(for basement or raised
termination installations)
982
Snorkel Termination (14" rise)
(for basement or raised
termination installations)
984
Horizontal Square Termination
950
Vinyl Siding Stand-off
991
High Wind Vertical
Termination
9 3 5 0 8 1 1 6
Elbows
990
90• Elbow
990B
90• Elbow, Black (interior)
Penetration, Support
942
Wall Thimble
941
Cathedral Ceiling Support Box
943
Flashing, 0/12 to 6/12 Roof Pitch
943S
Flashing, 7/12 to 12/12 Roof Pitch
953
Storm Collar
963
Ceiling Fire-stop
988
Wall Strap