Voltage Specifications; Output Tolerance Specifications; Output Feature Specifications; Battery Specifications - HP R1500 - UPS XR User Manual

Hp r1500 g3 ups user guide
Table of Contents

Advertisement

UPS model
R1500 G3 INTL

Voltage specifications

Configuration setting (VAC)
100
110
120
220
230
240

Output tolerance specifications

Source of power
Utility power (nominal
range)
Battery power

Output feature specifications

Feature
Online efficiency
Voltage wave shape
Surge suppression
Noise filtering

Battery specifications

Feature
Type
Voltage
Charging
IMPORTANT:
mode to float mode. For certain conditions such as heavily discharged batteries, battery
condition, and so on, it may take longer than usual to reach float mode. In these cases, it may take
longer than 48 hours to reach the rest mode.
VA
Nominal power
rating (W)
1500
1000
Available nominal output voltage (VAC)
100
110
120
220
230
240
Regulation
-10% to +6% of nominal output voltage rating (within the
guidelines of the Computer Business Equipment
Manufacturers Association)
±20% of nominal output voltage rating
Specification
95% nominal input voltage
Sine wave; 5% THD with typical PFC load
ANSI C62.41 Category A (formerly IEEE 587)
Full-time EMI/RFI filtering
Specification
6 V, 9 AH, sealed, maintenance-free, valve-regulated,
rechargeable, lead-acid battery.
The battery modules have a battery string voltage of 36 V.
Advanced charging for faster recovery. Complete charge takes at
least 48 hours. After approximately 24 hours, the batteries reach
90% charge at default nominal utility voltage and no load.
The 48-hour timer for the overall charge cycle triggers at the transition from charge
Nominal voltage
setting
220, 230, 240
Specifications 35