Fault Codes - Viessmann VITODENS 200-W Service Instructions Manual

Wall mounted gas condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Fault codes

Dis-
Const.
Weath.-
played
comp.
fault
code
10
X
X
18
X
X
20
X
X
28
X
X
30
X
X
38
X
X
40
X
44
X
System char-
Cause
acteristics
Regulates as if
Short circuit,
the outside
outside tem-
temperature
perature sen-
were 0 °C
sor
Regulates as if
Lead break,
the outside
outside tem-
temperature
perature sen-
were 0 °C
sor
Regulates with-
Short circuit,
out flow tem-
system flow
perature sen-
temperature
sor (low loss
sensor
header)
Regulates with-
Lead break,
out flow tem-
system flow
perature sen-
temperature
sor (low loss
sensor
header)
Burner blocked Short circuit,
boiler water
temperature
sensor
Burner blocked Lead break,
boiler water
temperature
sensor
Mixer closes
Short circuit,
flow tempera-
ture sensor,
heating circuit
2 (with mixer)
Mixer closes
Short circuit,
flow tempera-
ture sensor,
heating circuit
3 (with mixer)
Troubleshooting
Measures
Check the outside
temperature sen-
sor (see
page 109)
Check the outside
temperature sen-
sor (see
page 109)
Check the low loss
header sensor (see
page 111)
Check the low loss
header sensor (see
page 111)
Check the boiler
water temperature
sensor (see
page 111)
Check the boiler
water temperature
sensor (see
page 111)
Check flow temper-
ature sensor
Check flow temper-
ature sensor
97