Viessmann VITODENS 200-W Service Instructions Manual page 53

Wall mounted gas condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Heating circuit 1, heating circuit 2, heating...
Coding in the delivered condition
Pump control in "Standby mode"
F7:25
In the "Standby" operat-
ing mode, the circulation
pump in the heating cir-
cuit connection set is per-
manently ON (only for
constant temperature
control units)
Start temperature raising
F8:-5
Temperature limit for ter-
minating the reduced
mode -5 ºC, see example
on page 130.
Observe the setting of
coding address "A3" (only
for weather-compensa-
ted control units)
End temperature raising
F9:-14
Temperature limit for rais-
ing the reduced set room
temp. -14 ºC, see exam-
ple on page 130 (only for
weather-compensated
control units)
Increase set flow temperature
FA:20
Raising the set boiler
water temperature or the
set flow temperature
when changing from
operation with reduced
room temperature to
operation with standard
room temperature, by
20 %. See example on
page 131 (only for
weather-compensated
control units)
(cont.)
Possible change
F7:0
In the "Standby" operating
mode, the circulation pump
in the heating circuit con-
nection set is permanently
OFF
F7:1
In the "Standby" operating
to
mode, the circulation pump
F7:24
in the heating circuit con-
nection set will be started 1
to 24 times per day for
10 min respectively
F8:+10
Temperature limit adjusta-
to
ble from
F8:-60
+10 to -60 °C
F8:-61
Function disabled
F9:+10
Temperature limit for rais-
to
ing the set room tempera-
F9:-60
ture to the value selected
for standard mode adjusta-
ble from
+10 to -60 °C
FA:0
Temperature rise adjusta-
to
ble from 0 to 50 %
FA:50
Code 1
53

Hide quick links:

Advertisement