General/Group "1 - Viessmann VITODENS 200-W Service Instructions Manual

Wall mounted gas condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Code 2
Calling up coding level 2
4. Select group of the required coding
address with V/v. For example,
"1" for group "General" (see following
section):
Confirm selected group with OK.
5. Select coding address with V/v.
6. Select value according to the follow-
ing tables with V/v and confirm with
OK.

General/Group "1"

Select "General" for weather-compensated control units (see page 55).
Select "1" for constant temperature control units (see page 55).
Coding
Coding in the delivered condition
00:1
System version 1:
One heating circuit with-
out mixer (A1), without
DHW heating
Value
System
address
version
00: ...
2
1
3
2
4
2
5
3
6
3
56
(cont.)
7. If you want to reset all codes to
Possible change
00:2
to
00:10
Description
One heating circuit without mixer (heating circuit 1), with DHW
heating (code is adjusted automatically)
One heating circuit with mixer (heating circuit 2), without DHW
heating
One heating circuit with mixer (heating circuit 2), with DHW
heating
One heating circuit without mixer (heating circuit 1) and one
heating circuit with mixer (heating circuit 2), without DHW
heating (code is adjusted automatically)
One heating circuit without mixer (heating circuit 1) and one
heating circuit with mixer (heating circuit 2), with DHW heating
(code is adjusted automatically)
their delivered condition:
Select Ú "7" and confirm with OK.
When " " flashes, confirm with OK.
Note
This also resets codes from coding
level 1.
For system schemes, see
the following table: