Wall mounted gas condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Code 2
DHW/Group "3"
(cont.)
Coding in the delivered condition
62:2
Circulation pump with
2 min run-on time after
cylinder heating
63:0
Without auxiliary function
for DHW heating (only for
constant temperature
control units)
65:0
Do not adjust!
67:40
For solar DHW heating:
Set DHW temperature
40 °C. Reheating is sup-
pressed above the selec-
ted set temperature
(DHW heating blocked by
the boiler).
6C:100
Set speed; internal circu-
lation pump with DHW
heating 100 %
6F:...
Maximum output for
DHW heating in %, speci-
fied by the boiler coding
card
71:0
DHW circulation pump:
"ON" in accordance with
the time program (only for
weather-compensated
control units)
72:0
DHW circulation pump:
"ON" in accordance with
the time program (only for
weather-compensated
control units)
73:0
DHW circulation pump:
"ON" in accordance with
the time program (only for
weather-compensated
control units)
68
Possible change
62:0
Circulation pump without
run-on
62:1
Run-on time adjustable
to
from 1 to 15 min
62:15
63:1
Auxiliary function: 1 x daily
63:2
Every 2 days to every 14
to
days
63:14
63:15
2 x daily
67:0
Set DHW temperature
to
adjustable from 0 to 95 °C
67:95
(limited by boiler-specific
parameters)
6C:0
Set speed adjustable from
to
0 to 100 %
6C:100
6F:0
Max. output during DHW
to
heating adjustable from
6F:100
min. output to 100 %
71:1
"OFF" during DHW heating
to the first set value
71:2
"ON" during DHW heating
to the first set value
72:1
"OFF" during DHW heating
to the second set value
72:2
"ON" during DHW heating
to the second set value
73:1
"ON" from once per hour
to
for 5 min up to 6 times per
73:6
hour for 5 min during the
time program
73:7
Constantly "ON"