Viessmann VITODENS 200-W Service Instructions Manual page 79

Wall mounted gas condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Heating circuit 1, heating circuit 2, heating...
Coding in the delivered condition
A6:36
Extended economy func-
tion disabled (only for
weather-compensated
control units)
A7:0
Without mixer economy
function (only for a
weather-compensated
control unit and heating
circuit with mixer)
A8:1
Heating circuit with mixer
creates a demand for the
internal circulation pump
(only for weather-com-
pensated control units)
A9:7
With pump idle time:
Heating circuit pump
"OFF" if the set value
changes through a
change in operating
mode or through a
change in the set room
temperature (only for
weather-compensated
control units)
(cont.)
Possible change
A6:5
Extended economy control
to
enabled, i.e. the burner and
A6:35
heating circuit pump will be
switched OFF and the
mixer closed at a variable
adjustable value between 5
and 35 °C plus 1 °C. Base
value is the adjusted out-
side temperature. This
value is based on the
actual outside temperature
and a time constant that
takes the cooling down of
an average building into
consideration.
A7:1
With mixer economy func-
tion (extended heating cir-
cuit pump logic):
Heating circuit pump also
"OFF":
■ If a mixer has been
closed for longer than
20 min.
Heating pump "ON":
■ If the mixer changes to
control function
■ If there is a risk of frost
A8:0
Heating circuit with mixer
creates no demand for the
internal circulation pump
A9:0
Without pump idle time
A9:1
With pump idle time;
to
adjustable from 1 to 15
A9:15
Code 2
79