Code 2
Heating circuit 1, heating circuit 2, heating...
Coding in the delivered condition
d8:0
No heating program
changeover via extension
EA1
E2:50
With remote control: No
display correction for the
actual room temperature
(only for weather-com-
pensated control units)
E5:0
Without external variable
speed heating circuit
pump (only for weather-
compensated control
units)
E6:...
Maximum speed of the
variable speed heating
circuit pump in % of the
max. speed in standard
mode. Value is defaulted
by boiler-specific param-
eters (only for weather-
compensated control
units).
E7:30
Minimum speed of the
variable speed heating
circuit pump: 30 % of the
maximum speed (only for
weather-compensated
control units)
82
(cont.)
Possible change
d8:1
Heating program change-
over via input DE1 at exten-
sion EA1
d8:2
Heating program change-
over via input DE2 at exten-
sion EA1
d8:3
Heating program change-
over via input DE3 at exten-
sion EA1
E2:0
Display correction -5 K
to
to
E2:49
Display correction -0.1 K
E2:51
Display correction +0.1 K
to
to
E2:99
Display correction +4.9 K
E5:1
With external variable
speed heating circuit pump
(automatic recognition)
E6:0
Maximum speed adjusta-
to
ble from 0 to 100 %
E6:100
E7:0
Minimum speed adjustable
to
from 0 to 100 % of the max-
E7:100
imum speed