Viessmann VITODENS 200-W Service Instructions Manual page 75

Wall mounted gas condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Solar/Group "4"
(cont.)
Coding in the delivered condition
25:50
Stop temperature for the
thermostat function
50 °C.
Start temperature for the
thermostat function ≤
stop temperature for the
thermostat function:
Thermostat function e.g.
for reheating. Switching
output sS is switched
OFF when the tempera-
ture at sensor /
exceeds the start temper-
ature for the thermostat
function.
Start temperature for
thermostat function >
stop temperature for ther-
mostat function:
Thermostat function e.g.
for utilising excess heat.
Switching output sS is
switched OFF when the
temperature at sen-
sor / falls below the
start temperature for the
thermostat function.
26:1
Priority for DHW cylinder
1 – with alternate heat-
ing
Only when setting code
20:8.
Possible change
25:0
Start temperature for ther-
to
mostat function is adjusta-
25:100
ble from 0 to 100 K
26:0
Priority for DHW cylinder 1
– without alternate heating
26:2
Priority for DHW cylinder 2
– without alternate heating
26:3
Priority for DHW cylinder 2
– with alternate heating
26:4
Alternate heating without
priority for one DHW cylin-
der
Code 2
75