Viessmann VITODENS 200-W Service Instructions Manual page 51

Wall mounted gas condensing boiler natural gas and lpg version
Table of Contents

Advertisement

Heating circuit 1, heating circuit 2, heating...
Coding in the delivered condition
Flow temperature maximum limit
C6:74
Electronic maximum flow
temperature limited to
74 °C (only for weather-
compensated control
units)
Heating program - changeover
d5:0
The external heating pro-
gram changeover
changes the heating pro-
gram to "Constant opera-
tion with reduced room
temperature" or "Standby
mode" (only for weather-
compensated control
units)
Ext. heating program changeover to heating circuit
d8:0
No heating program
changeover via extension
EA1
Max. pump speed in standard mode
E6:...
Maximum speed of the
variable speed heating
circuit pump in % of the
max. speed in standard
mode. Value is defaulted
by boiler-specific param-
eters (only for weather-
compensated control
units).
(cont.)
Possible change
C6:10
Maximum limit adjustable
to
from 10 to 127 °C (limited
C6:127
by boiler-specific parame-
ters)
d5:1
The external heating pro-
gram changeover changes
to "Constant operation with
standard room tempera-
ture" (independent of cod-
ing address 3A, 3b and
3C)
d8:1
Heating program change-
over via input DE1 at exten-
sion EA1
d8:2
Heating program change-
over via input DE2 at exten-
sion EA1
d8:3
Heating program change-
over via input DE3 at exten-
sion EA1
E6:0
Maximum speed adjusta-
to
ble from 0 to 100 %
E6:100
Code 1
51