8.5.2 Errors and Countermeasures

The table below shows a summary of error messages.
Table 8.5.1 Error Message Summary
Integral
Indicator
Display
None
----
Er. 01
Er. 02
Er. 03
Er. 04
Er. 05
Er. 06
Er. 07
Er. 08
Er. 09
Er. 10
Er. 11
Er. 12
*1: For Model EJA510A and EJA530A, this error code appears when an illegal overpressure is
applied to the pressure sensor in addition to the capsule problem. The Er. 01 will remain even if
the normal input pressure is regained.
*2: For Model EJA510A and EJA530A, restart the power to the transmitter. Then if no error code
appears, perform necessary adjustments such as zero-adjustment to continue the operation.
If the error code still exists, replace the capsule assembly.
*3: For Model EJA120A, static pressure cannot be measured. The display is always 0 MPa, but this is
not a measured value.
BT200 Display
Cause
GOOD
ERROR
Capsule problem.
CAP MODULE
FAULT
AMP MODULE
Amplifier problem.
FAULT
OUT OF RANGE
Input is outside
measurement range
limit of capsule.
OUT OF SP
Static pressure
RANGE
exceeds specified
*3
range.
OVER TEMP
Capsule temperature
(CAP)
is outside range
(–50 to 130°C).
OVER TEMP
Amplifier temperature
(AMP)
is outside range
(–50 to 95°C).
OVER OUTPUT
Output is outside high
or low range limit
value.
OVER DISPLAY
Displayed value is
outside high or low
range limit value.
ILLEGAL LRV
LRV is outside setting
range.
ILLEGAL HRV
HRV is outside setting
range.
ILLEGAL SPAN
SPAN is outside
setting range.
ZERO ADJ OVER
Zero adjustment is too
large.
8. BRAIN TERMINAL BT200 OPERATION
Output Operation
during Error
*1
Outputs the signal
(Hold, High, or Low)
set with parameter
D53.
Outputs the signal
(Hold, High, or Low)
set with parameter
D53.
Outputs high range
limit value or low
range limit value.
Displays present
output.
Displays present
output.
Displays present
output.
Outputs high or low
range limit value.
Displays high or low
range limit value.
Holds output
immediately before
error occurrence.
Holds output
immediately before
error occurrence.
Holds output
immediately before
error occurrence.
Displays present
output.
8-19
Countermeasure
*2
Replace capsule.
Replace amplifier.
Check input.
Check line pressure
(static pressure).
Use heat insulation or
make lagging to keep
temperature within
range.
Use heat insulation or
make lagging to keep
temperature within
range.
Check input and range
setting, and change
them as needed.
Check input and
display conditions and
modify them as
needed.
Check LRV and
modify as needed.
Check HRV and
modify as needed.
Check SPAN and
change as needed.
Readjust zero point.
T0811 .EPS