b. Setting Calibration Range Lower
Range Value and Higher Range Value
(C21: LOW RANGE, C22: HIGH
RANGE)
These range values are set as specified in the order
before the instrument is shipped. Follow the procedure
below to change the range.
• The measurement span is determined by the high and
low range limit values. In this instrument, changing
the low range value also automatically changes the
high range value, keeping the span constant.
• Example 1: With present settings of 0 to 30 kPa,
set the lower range value to 0.5 kPa.
SET
Set 0.5.
C21:LOW RANGE
0 kPa
Press the
+
0.5
enter the setting.
DEL
CLR
ESC
SET
Press the
C21:LOW RANGE
0.5 kPa
FEED
NO
OK
SET
The higher range value is changed
C20:PRESS UNIT
kPa
while the span remains constant.
C21:LOW RANGE
0.5 kPa
C22:HIGH RANGE
30.5 kPa
DATA
DIAG
PRNT
ESC
Span = Higher range value – Lower range value
• Note, however, that changing the higher range value
does not cause the lower range value to change.
Thus, changing the higher range value also changes
the span.
• Calibration range can be specified with range value
specifications up to 5 digits (excluding any decimal
point) for low or high range limits within the range
of –32000 to 32000.
key twice to
(OK) key.
F0813.EPS
8-8
8. BRAIN TERMINAL BT200 OPERATION
• Example 2: With present settings of 0 to 30 kPa,
set the Higher range value to10 kPa.
Set 10.
SET
C22:HIGH RANGE
30 kPa
Press the
+
10
to enter the setting.
DEL
CLR
ESC
SET
Press the
C22:HIGH RANGE
10 kPa
FEED
NO
OK
PARAM
The low range value is not
C20:PRESS UNIT
changed, so the span changes.
kPa
C21:LOW RANGE
0 kPa
C22:HIGH RANGE
10 kPa
DATA
DIAG
PRNT
ESC

(3) Damping Time Constant Setup

(C30: AMP DAMPING)
When the instrument is shipped, the damping time
constant is set at 2.0 seconds. Follow the procedure
below to change the time constant.
• Example: Change from 2.0 sec to 4.0 sec.
SET
Use the
C30:AMP DAMPING
2.0 sec
select 4.0 sec.
<
2.0 sec
>
<
4.0 sec
>
Press the
<
8.0 sec
>
<
16.0 sec
>
enter the setting.
ESC
SET
Press the
C30:AMP DAMPING
4.0 sec
FEED
NO
OK
0.2sec
0.5sec
1.0sec
2.0sec
4.0sec
8.0sec
16.0sec
32.0sec
64.0sec
Note: The damping time constant set here is the damping time
constant for the amplifier assembly. The damping time
constant for the entire transmitter is the sum of the values for
the amplifier assembly and for the capsule assembly. For the
capsule assembly damping time constant (fixed), see the
"General Specifications" found at the end of this manual.
(See Chapter 10.)
key twice
(OK) key.
F0814.EPS
or
key to
key twice to
(OK) key.
F0815.EPS
IM 01C21B01-01E