Errors And Countermeasures - YOKOGAWA DPharp EJA110A User Manual

Eja series differential pressure and pressure transmitters
Hide thumbs Also See for DPharp EJA110A:
Table of Contents

Advertisement

7.

Errors and Countermeasures

NOTE
For F
Fieldbus and PROFIBUS PA communication types, please refer to manuals in the attached CD-ROM.
OUNDATION
The table below shows a summary of error messages for BRAIN and HART protocols.
Table 7.1
Error Message Summary
Integral
Indicator
Description
Display
None
GOOD
---
ERROR
Er. 01
CAP MODULE FAULT
Er. 02
AMP MODULE FAULT
Er. 03
OUT OF RANGE
Er. 04
OUT OF SP RANGE
Er. 05
OVER TEMP (CAP)
Er. 06
OVER TEMP (AMP)
Er. 07
OVER OUTPUT
Er. 08
OVER DISPLAY
Er. 09
ILLEGAL LRV
Er. 10
ILLEGAL URV
Er. 11
ILLEGAL SPAN
Er. 12
ZERO ADJ OVER
*1:
This error code appears at a capsule problem or when an illegal overpressure is applied to the pressure sensor.
*2:
If the normal pressure is regained, the Er.01 will disappear according to the setting of the parameter of E50 AUTO RECOVER.
When the E50 AUTO RECOVER is set to ON, the Er.01 will disappear automatically. The default setting for this parameter is
ON. When the E50 AUTO RECOVER is set to OFF, restart the transmitter to cancel Er.01. If no error code appears then, perform
necessary adjustments such as zero-adjustment to continue the operation. If the error code still appears, replace the capsule
assembly.
*3:
For Model EJA120A, static pressure cannot be measured. The display is always 0 MPa, but this is not a measured value.
<7.
Cause
Output Operation during Error
Capsule problem.*
1
Outputs the signal according to
status of a burnout direction pin
or switch (the signal can be set as
"hold" for BRAIN protocol).
Amplifi er problem.
Outputs the signal (Hold, Outputs
the signal according to status of
a burnout direction pin or switch
(the signal can be set as "hold" for
BRAIN protocol).
Input is outside
Outputs high range limit value or
measurement range limit
low range limit value.
of capsule.
Static pressure exceeds
Displays present output.
specifi ed range.*
3
Capsule temperature
Displays present output.
is outside range (-50 to
130°C).
Amplifi er temperature
Displays present output.
is outside range (-50 to
95°C).
Output is outside high or
Outputs high or low range limit
low range limit value.
value.
Displayed value is
Displays high or low range limit
outside high or low range
value.
limit value.
LRV is outside setting
Holds output immediately before
range.
error occurrence.
URV is outside setting
Holds output immediately before
range.
error occurrence.
SPAN is outside setting
Holds output immediately before
range.
error occurrence.
Zero adjustment is too
Displays present output.
large.
Errors and Countermeasures
28
>
Countermeasure
Replace the capsule when
error keeps appearing even
after restart.*
2
Replace amplifi er.
Check input.
Check line pressure (static
pressure).
Use heat insulation or make
lagging to keep temperature
within range.
Use heat insulation or make
lagging to keep temperature
within range.
Check input and range
setting, and change them as
needed.
Check input and display
conditions and modify them
as needed.
Check LRV and modify as
needed.
Check URV and modify as
needed.
Check SPAN and change as
needed.
Readjust zero point.
IM 01C22A01-01E