Csa Certification - YOKOGAWA Dpharp vigilantplant EJA110A User Manual

Differential pressure transmitters
Hide thumbs Also See for Dpharp vigilantplant EJA110A:
Table of Contents

Advertisement

• Take care not to generate mechanical sparking
when accessing to the instrument and peripheral
devices in a hazardous location.
Note 4. Maintenance and Repair
• The instrument modification or parts replacement
by other than authorized representative of
Yokogawa Electric Corporation is prohibited and
will void Factory Mutual Explosionproof Approval.
c. FM Intrinsically Safe Type/FM
Explosionproof Type
Model EJA Series pressure transmitters with
optional code /FU1 can be selected the type of
protection (FM Intrinsically Safe or FM
Explosionproof) for use in hazardous locations.
Note 1. For the installation of this transmitter,
once a particular type of protection is
selected, any other type of protection
cannot be used. The installation must be
in accordance with the description about
the type of protection in this instruction
manual.
Note 2. In order to avoid confusion, unnecessary
marking is crossed out on the label other
than the selected type of protection when
the transmitter is installed.

2.9.2 CSA Certification

a. CSA Intrinsically Safe Type
Caution for CSA Intrinsically safe type. (Following
contents refer to "DOC No. ICS003-A12 P.1-1 and
P.1-2.")
Note 1. Model EJA Series differential, gauge, and
absolute pressure transmitters with
optional code /CS1 are applicable for use
in hazardous locations
Certificate: 1053843
• Applicable Standard: C22.2 No.0, No.0.4, No.25,
No.30, No.94, No.142, No.157, No.213
• Intrinsically Safe for Class I, Division 1, Groups A,
B, C & D. Class II, Division 1, Groups E, F & G
and Class III, Division 1 Hazardous Locations.
• Nonincendive for Class I, Division 2, Groups A, B,
C & D, Class II, Division 2, Groups F & G, and
Class III, Hazardous Locations. (not use Safety
Barrier)
• Encl. "Type 4X"
• Temperature Class: T4
• Ambient temperature: –40 to 60°C
• Process Temperature: 120°C max.
Note 2. Entity Parameters
• Intrinsically safe ratings are as follows:
Maximum Input Voltage (Vmax) = 30 V
Maximum Input Current (Imax) = 165 mA
Maximum Input Power (Pmax) = 0.9 W
Maximum Internal Capacitance (Ci) = 22.5 nF
Maximum Internal Inductance (Li) = 730 μH
* Associated apparatus (CSA certified barriers)
Maximum output voltage (Voc)
Maximum output current (Isc)
Maximum output power (Pmax)
Note 3. Installation
• All wiring shall comply with Canadian Electrical
Code Part I and Local Electrical Codes.
• The instrument modification or parts replacement
by other than authorized representative of
Yokogawa Electric Corporation and Yokogawa
Corporation of America is prohibited and will void
Canadian Standards Intrinsically safe and
nonincendive Certification.
[Intrinsically Safe]
Hazardous Location
Class I, II, III, Division 1,
Groups A, B, C, D, E, F, G
EJA Series Pressure
Transmitters
+
Supply
[Nonincendive]
Hazardous Location
Class I, II, Division 2,
Groups A, B, C, D, E, F, G
Class III, Division 1.
EJA Series Pressure
Transmitters
+
Supply
b. CSA Explosionproof Type
Caution for CSA explosionproof type.
Note 1. Model EJA Series differential, gauge, and
absolute pressure transmitters with
optional code /CF1 are applicable for use
in hazardous locations:
Certificate: 1089598
• Applicable Standard: C22.2 No.0, No.0.4, No.25,
No.30, No.94, No.142
• Explosionproof for Class I, Division 1, Groups B,
C and D.
• Dust-ignitionproof for Class II/III, Division 1,
Groups E, F and G.
2-5
2. HANDLING CAUTIONS
30 V
165 mA
0.9 W
Nonhazardous Location
General
Purpose
Safety Barrier
Equipment
+
+
+
Nonhazardous Location
General
Purpose
Equipment
+
Not Use
Safety Barrier
F0204.EPS
IM 01C21B01-01E

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dpharp eja120aDpharp eja130a

Table of Contents