8.3 Setting Parameters Using the BT200

8.3.1 Parameter Summary

Instruments to which applicable:
F: Differential pressure transmitters
P: Pressure transmitters
L: Liquid level transmitters
No.
Item
Description
01
Model+capsule type
MODEL
02
TAG NO.
Tag number
03 SELF CHECK
Self-diagnostic result
A
DISPLAY
Measured data display
A10 OUTPUT (%)
Output (in %)
A11 ENGR.
Output (in engineering
OUTPUT
units)
A20 AMP TEMP
Amplifier temperature
A21 CAPSULE
Capsule temperature
TEMP
A30 STATIC
Static pressure
PRESS
A40 INPUT
Input (indicated as the
value after zeroing)
A60 SELF CHECK
Self-diagnostic
messages
B
SENSOR
Sensor type
TYPE
B10 MODEL
Model+span
B11 STYLE NO.
Style number
B20 LRL
Lower range-limit
B21 URL
Upper range-limit
B30 MIN SPAN
Minimum span
B40
MAX STAT.P.
Maximum static
pressure*
B60 SELF CHECK
Self-diagnostic
messages
C
SETTING
Setting data
C10 TAG. NO.
Tag number
C20 PRESS UNIT
Measurement range
units
C21 LOW RANGE
Measurement range,
lower range value
C22 HIGH
Measurement range,
RANGE
higher range value
C30 AMP
Damping time constant
DAMPING
C40 OUTPUT
Output mode and
integral indicator mode
MODE
C60
SELF CHECK
Self-diagnostic
messages
D
AUX SET 1
Auxiliary setting data 1
D10 LOW CUT
Low cut
D11 LOW CUT
Low cut mode
MODE
D20 DISP SELECT
Display selection
D21 DISP UNIT
Engineering unit for
display
D22 DISP LRV
Engineering range,
lower range value
D23 DISP HRV
Engineering range,
higher range value
EJA110A, EJA120A, and EJA130A
EJA310A, EJA430A, EJA440A, EJA510A, and EJA530A
EJA210A and EJA220A
Rewrita-
bility
16 alphanumerics
GOOD/ERROR
Menu name
–5 to 110%*
–19999 to 19999
Unit specified in D30
Unit specified in D30
Unit specified in D31*
–32000 to 32000
GOOD/ERROR, CAP MODULE FAULT, AMP MODULE FAULT,
OUT OF RANGE, OUT OF SP RANGE*
OVER TEMP (AMP), OVER OUTPUT, OVER DISPLAY,
ILLEGAL LRV, ILLEGAL HRV, ILLEGAL SPAN, and
ZERO ADJ OVER
Menu name
16 uppercase alphanumerics
–32000 to 32000
–32000 to 32000
–32000 to 32000
4
Same as A60
Menu name
16 alphanumerics
Selected from mmH
mmWG, mmHg, Torr, Pa, hPa, kPa,
MPa, mbar, bar, gf/cm
inH
–32000 to 32000(but within
measurement range)
–32000 to 32000(but within
measurement range)
Selected from 0.2*
4.0, 8.0, 16.0, 32.0, or 64.0 sec.
Selected from OUT:LIN; DSP:LIN,
OUT:LIN; DSP:SQR,
OUT:SQR; DSP:SQR
Same as A60
Menu name
0.0 to 20.0%
LINEAR/ZERO
NORMAL %/USER SET,
USER & %/INP PRES, PRES & %
8 uppercase
alphanumerics
–19999 to 19999
–19999 to 19999
Remarks
3
1
O, mmAq,
2
2
2
, kgf/cm
O, inHg, ftH
O, psi, or atm
2
2
2
, 0.5, 1.0, 2.0,
8-4
8. BRAIN TERMINAL BT200 OPERATION
Default Value
1
, OVER TEMP (CAP),
As specified when ordered.
As specified when ordered.
,
As specified when ordered.
As specified when ordered.
2.0 s
As specified when ordered.
If not specified,
OUT: LIN; DSP: LIN.
10.0%
LINEAR
As specified when ordered.
As specified when ordered.
As specified when ordered.
Applica-
bility
F
P L
T0805.EPS
IM 01C21B01-01E