Integral Indicator Scale Setup - YOKOGAWA Dpharp vigilantplant EJA110A User Manual

Differential pressure transmitters
Hide thumbs Also See for Dpharp vigilantplant EJA110A:
Table of Contents

Advertisement

(6) Integral Indicator Scale Setup

The following 5 displays are available for integral
indicators.
D20: DISP SELECT
and Display
NORMAL %
Indicates –5 to 110% range
depending on the Measurement
range (C21, C22).
USER SET
Indicates values depending on the
Engineering range (D22, D23).
Units set using Engineering unit
(D21) are not indicated.
USER & %
Indicates user set and % alternately
in 3 second intervals.
INP PRES
Indicates input pressure.
Indication limits –19999 to 19999.
PRES & %
Indicates input pressure and %
alternately in 3 second intervals.
(Note 1) Scale range can be specified with range limit specifications up
to 5 digits (excluding any decimal point) for low or high range
limits within the range of –19999 to 19999.
The range with decimals is available to the third decimal place.
(Note 2) It indicates the value after zeroing.
See (a.) through (c.) for each setting procedure.
Description
and Related parameters
A10:OUTPUT (%)
45.6 %
Note 1
(
A11:ENGR.OUTPUT
20.0 M
A10:OUTPUT (%)
45.6 %
A11:ENGR. OUTPUT
20.0 M
Note 2
(
)
A40:INPUT
456 kPa
A10:OUTPUT (%)
45.6 %
A40:INPUT
456 kPa
T0808.EPS
8. BRAIN TERMINAL BT200 OPERATION
% indication and
input pressure
indication
D20: DISP SELECT
NORMAL %
INP PRES
PRES & %
Transmitter is set
for "% display" when
shipped.
)
a. Display Selection (D20: DISP SELECT)
Follow the instructions given to the below to change
the range of integral indication scales.
When USER SET is selected, the user set values of
integral indication and A11: ENGR. OUTPUT
parameter are indicated.
• Example: Set the integral indicator scale to
engineering units display.
SET
D20:DISP SELECT
NORMAL %
<NORMAL %>
<USER SET>
<USER & %>
<INP PRES>
SET
D20:DISP SELECT
USER SET
FEED
NO
The "%" disappears from the
integral indicator display.
8-10
User-set engineering
unit display
D20: DISP SELECT
USER SET
USER & %
Set for user-set
engineering unit display.
D21: DISP UNIT
Set a unit to be
displayed on the BT200.
D22: DISP LRV
Set a numeric value for
engineering unit for 4 mA
output (LRV).
D23: DISP HRV
Set a numeric value for
engineering unit for 20 mA
output (HRV).
Use the
or
to select "USER SET."
Press the
key twice to
ESC
enter the setting.
Press the
(OK) key.
OK
IM 01C21B01-01E
F0818.EPS