Setting Parameters; Tag No. Setup; Calibration Range Setup - YOKOGAWA Dpharp vigilantplant EJA110A User Manual

Differential pressure transmitters
Hide thumbs Also See for Dpharp vigilantplant EJA110A:
Table of Contents

Advertisement

8.3.3 Setting Parameters

Set or change the parameters as necessary. After
completing these, do not fail to use the "DIAG" key to
confirm that "GOOD" is displayed for the self-
diagnostic result at _60: SELF CHECK.
(1) Tag No. Setup (C10: TAG NO)
Use the procedure below to change the Tag No. Up to
16 alphanumeric characters can be entered.
• Example: Set a Tag No. to FIC-1a
<When power is off>
––WELCOME––
BRAIN TERMINAL
ID:
BT200
check connection
push ENTER key
UTIL
FEED
PARAM
01:MODEL
EJA110A-DM
02:TAG NO.
YOKOGAWA
03:SELF CHECK
GOOD
OK
MENU
A:DISPLAY
B:SENSOR TYPE
HOME
SET
ADJ
ESC
MENU
C:SETTING
D:AUX SET 1
E:AUX SET 2
H:AUTO SET
HOME
SET
ADJ
ESC
MENU
C10:TAG NO.
YOKOGAWA
C20:PRESS UNIT
kPa
C21:LOW RANGE
0 kPa
DATA
DIAG
PRNT
ESC
SET
C10:TAG NO.
YOKOGAWA
YOKOGAWA
CODE
CAPS
CLR
ESC
SET
C10:TAG NO.
YOKOGAWA
FIC-1a _
CODE
caps
CLE
ESC
When you have made an entry mistake, return
the cursor
Press the
key to turn on
the BT200.
Connect DPharp and BT200 using
a communication cable and press
the
key.
Displays the name of connected
DPharp model, TAG NO. and
diagnostics information. Press the
(OK) key after confirmation.
Press the
(SET) key to
display the SET menu panel.
Select C: SETTING and press the
key.
Select C10: TAG NO. and press
the
key.
Set the new TAG NO. (FIC-1a).
FOKOGAWA
FIKOGAWA
FICOGAWA
FIC-GAWA
FIC-1AWA
FIC-1aWA
FIC-1a
Set TAG NO. and press the
key.
using the key, then reenter.
SET
C10:TAG NO.
YOKOGAWA
FIC-1a
PRINTER OFF
F2:PRINTER ON
FEED
POFF
SET
C10:TAG NO.
FIC-1a
FEED
PARAM
C10:TAG NO.
FIC-1a
C20:PRESS UNIT
kPa
C21:LOW RANGE
0 kPa
DATA
DIAG

(2) Calibration Range Setup

a. Setting Calibration Range Unit
(C20: PRESS UNIT)
The unit is set at the factory before shipment if
specified at the time of order. Follow the procedure
below to change the unit.
• Example: Change the unit from mmH
SET
C20:PRESS UNIT
mmH20
< mmWG >
< mmHG >
< Torr >
< kPa
>
SET
C20:PRESS UNIT
kPa
FEED
mmH
O
2
mmAq
mmWG
mmHg
Torr
kPa
MPa
mbar
bar
gf/cm
kgf/cm
inH
O
2
inHg
ftH
O
2
psi
atm
F0810.EPS
8-7
8. BRAIN TERMINAL BT200 OPERATION
This is the panel for confirming
set data. The set data items flash.
When all items have been confir-
med, press the
NO
again. (To go back to the setting
panel, press the
The DPharp TAG NO. was
overwritten.
Press the
return to the parameter panel.
NO
OK
Press the
return to the setting panel.
PRNT
ESC
Use the
key to select "kPa."
Press the
to enter the setting.
ESC
Press the
NO
OK
2
2
(NO) key.
(OK) key to
(NO) key to
F0811.EPS
O to kPa.
2
or
key twice
(OK) key.
F0812.EPS
IM 01C21B01-01E

Advertisement